Wolf FB363 Instrucciones de operaciones Pagina 47

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 46
3062449_0309 47
Falling header temperature:
Sa_ist ≤ Sa_Soll - hysteresis, parallel mode
all mixers towards "CLOSE".
Sa_ist ≤ Sp_soll
all mixers towards "CLOSE" and all heating circuit pumps as
well as all primary pumps at the mixer modules (for cylinder and
convector heaters) "OFF"
Rising header temperature:
Sa_ist > Sp_soll + 2 K
all mixers towards "CLOSE" and all heating circuit pumps as
well as all primary pumps at the mixer modules (for cylinder and
convector heaters) "ON"
Sa_ist ≤ Sa_Soll - hysteresis, parallel mode + 2 K
no forced output
Sample diagram: Set cylinder temperature = 55 °C
Parameter MI 17 = 10 K
Parameter KM 22 = 5 K
Actual header temperature [K]
Forced actuation
Mixer "CLOSE"
Mixer "CLOSE" and pump "OFF"
Time
Parameters / Function description
Vista de pagina 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 59 60